Back to the backflow review queue

Backflow assembly test: Two Rivers Medical Offices

Approved

Filed Jun 17, 2025 by Cameron Vance, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 17, 2025
Assembly type
RP
Serial number
K664227
Size
4
Test gauge serial
G-6835
Gauge calibration date
Dec 26, 2024
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Vance, current on the service date
  • All required fields present
  • Address matches parcel 107-63-01219
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1953 Sycamore Ct
Owner: Calloway Holdings LLC
Parcel 107-63-01219