Backflow assembly test: Maple Leaf Brewing Co
ApprovedFiled Aug 2, 2025 by Morgan Pruitt, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 2, 2025
- Assembly type
- DC
- Serial number
- A644440
- Size
- 1 1/2
- Test gauge serial
- G-3545
- Gauge calibration date
- Apr 8, 2025
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Pruitt, current on the service date
- All required fields present
- Address matches parcel 107-84-01268
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6298 Fox Run Trl
Owner: Okafor Holdings LLC
Parcel 107-84-01268