Backflow assembly test: 1077 Orchard Trl

Approved

Filed Apr 9, 2025 by Jordan Brandt, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 9, 2025
Assembly type
RP
Serial number
A630752
Size
3/4
Test gauge serial
G-6450
Gauge calibration date
Mar 8, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 107-85-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1077 Orchard Trl
Owner: Riley Nguyen
Parcel 107-85-01296