Backflow assembly test: 7182 Fox Run Trl
ApprovedFiled Jul 31, 2026 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 31, 2026
- Assembly type
- DC
- Serial number
- Z938834
- Size
- 3/4
- Test gauge serial
- G-4413
- Gauge calibration date
- Nov 9, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Stroud, current on the service date
- All required fields present
- Address matches parcel 107-18-01180
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.