Back to the backflow review queue
Backflow assembly test: Hilltop Taqueria
ApprovedFiled Apr 11, 2026 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 11, 2026
- Assembly type
- RP
- Serial number
- B496387
- Size
- 2
- Test gauge serial
- G-1398
- Gauge calibration date
- Dec 5, 2025
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Stroud, current on the service date
- All required fields present
- Address matches parcel 107-84-01333
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4764 Cedar Hollow Ln
Owner: Nguyen Holdings LLC
Parcel 107-84-01333