Back to the backflow review queue

Backflow assembly test: 8869 Fox Run Dr

Approved

Filed Dec 17, 2025 by Riley Ramirez, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 17, 2025
Assembly type
DC
Serial number
A201413
Size
1
Test gauge serial
G-2458
Gauge calibration date
Nov 17, 2025
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 107-11-01282
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8869 Fox Run Dr
Owner: Avery Kessler
Parcel 107-11-01282