Backflow assembly test: 7613 Old Church Dr

Approved

Filed Oct 7, 2024 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 7, 2024
Assembly type
PVB
Serial number
B765840
Size
1
Test gauge serial
G-9637
Gauge calibration date
Mar 4, 2024
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Stroud, current on the service date
  • All required fields present
  • Address matches parcel 107-99-01077
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.