Backflow assembly test: 9339 Laurel Trl

Approved

Filed Mar 30, 2026 by Morgan Pruitt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 30, 2026
Assembly type
RP
Serial number
Z102124
Size
1
Test gauge serial
G-6063
Gauge calibration date
Sep 1, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 107-23-01153
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9339 Laurel Trl
Owner: Shawn Lindqvist
Parcel 107-23-01153