Back to the backflow review queue
Backflow assembly test: Corner Brewing Co
ApprovedFiled Jan 23, 2024 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 23, 2024
- Assembly type
- RP
- Serial number
- K807101
- Size
- 2
- Test gauge serial
- G-4480
- Gauge calibration date
- Sep 11, 2023
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Stroud, current on the service date
- All required fields present
- Address matches parcel 107-23-01059
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
964 Old Church Dr
Owner: Vance Holdings LLC
Parcel 107-23-01059