Backflow assembly test: 833 Quarry Trl

Approved

Filed Feb 5, 2025 by Riley Ramirez, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Feb 5, 2025
Assembly type
DC
Serial number
W142137
Size
1
Test gauge serial
G-7246
Gauge calibration date
Oct 21, 2024
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 107-61-01294
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.