Back to the backflow review queue

Backflow assembly test: 9339 Laurel Trl

Approved

Filed Feb 6, 2024 by Parker Fairley, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Feb 6, 2024
Assembly type
RP
Serial number
Z102124
Size
1
Test gauge serial
G-1730
Gauge calibration date
Sep 27, 2023
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 107-23-01153
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9339 Laurel Trl
Owner: Shawn Lindqvist
Parcel 107-23-01153