Backflow assembly test: 5635 Hickory Dr

Filed Nov 29, 2026 by Parker Fairley, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Nov 29, 2026
Assembly type
RP
Serial number
Z501946
Size
1
Test gauge serial
G-7639
Gauge calibration date
Aug 21, 2025
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
3.6 psid
Relief valve opened at
2.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 107-22-01068
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Property

5635 Hickory Dr
Owner: Reese Stroud
Parcel 107-22-01068