Backflow assembly test: Two Rivers Animal Hospital

Approved

Filed Nov 26, 2023 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 26, 2023
Assembly type
RP
Serial number
B969517
Size
2
Test gauge serial
G-9400
Gauge calibration date
May 4, 2023
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Stroud, current on the service date
  • All required fields present
  • Address matches parcel 107-65-01239
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2124 Cedar Hollow Ct
Owner: Benton Holdings LLC
Parcel 107-65-01239