Back to the backflow review queue

Backflow assembly test: Hilltop Market

Approved

Filed Jul 24, 2026 by Jordan Brandt, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jul 24, 2026
Assembly type
RP
Serial number
K457790
Size
4
Test gauge serial
G-1227
Gauge calibration date
Feb 28, 2026
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 107-21-01218
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3177 Cedar Hollow Ct
Owner: Okafor Holdings LLC
Parcel 107-21-01218