Back to the backflow review queue

Backflow assembly test: 7579 Mill Creek Trl

Approved

Filed Mar 22, 2025 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 22, 2025
Assembly type
PVB
Serial number
B950160
Size
1
Test gauge serial
G-4725
Gauge calibration date
Jan 22, 2025
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-90-01146
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7579 Mill Creek Trl
Owner: Emerson Ramirez
Parcel 097-90-01146