Back to the backflow review queue
Backflow assembly test: Main Street Self Storage
ApprovedFiled Oct 15, 2024 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 15, 2024
- Assembly type
- RP
- Serial number
- B729564
- Size
- 1 1/2
- Test gauge serial
- G-6938
- Gauge calibration date
- Feb 6, 2024
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Kessler, current on the service date
- All required fields present
- Address matches parcel 097-96-01139
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9087 Mill Creek Trl
Owner: Brandt Holdings LLC
Parcel 097-96-01139