Backflow assembly test: 1926 Sycamore Dr
ApprovedFiled Mar 11, 2026 by Taylor Whitcomb, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Mar 11, 2026
- Assembly type
- RP
- Serial number
- B993796
- Size
- 1
- Test gauge serial
- G-9301
- Gauge calibration date
- Jan 5, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Whitcomb, current on the service date
- All required fields present
- Address matches parcel 097-98-01037
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1926 Sycamore Dr
Owner: Rowan Marsh
Parcel 097-98-01037