Backflow assembly test: Golden Dental

Approved

Filed May 29, 2024 by Drew Okafor, Ridge Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 29, 2024
Assembly type
RP
Serial number
K727112
Size
1 1/2
Test gauge serial
G-6746
Gauge calibration date
Feb 9, 2023
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
2.4 psid
Relief valve opened at
3.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Okafor, current on the service date
  • All required fields present
  • Address matches parcel 097-95-01166
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.