Backflow assembly test: Main Street Animal Hospital

Approved

Filed Nov 12, 2025 by Taylor Whitcomb, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Nov 12, 2025
Assembly type
DC
Serial number
Z318426
Size
2
Test gauge serial
G-6766
Gauge calibration date
Jun 3, 2025
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 097-26-01311
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7527 Mill Creek Ln
Owner: Hollins Holdings LLC
Parcel 097-26-01311