Backflow assembly test: 6463 Pine Knoll Ct
ApprovedFiled Dec 12, 2023 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 12, 2023
- Assembly type
- DC
- Serial number
- B944580
- Size
- 3/4
- Test gauge serial
- G-7194
- Gauge calibration date
- Jun 6, 2023
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Kessler, current on the service date
- All required fields present
- Address matches parcel 097-89-01210
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6463 Pine Knoll Ct
Owner: Rowan Stroud
Parcel 097-89-01210