Back to the backflow review queue

Backflow assembly test: 4281 Meadow Lark Way

Filed Nov 29, 2026 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 29, 2026
Assembly type
RP
Serial number
K304845
Size
1
Test gauge serial
G-6244
Gauge calibration date
Jul 1, 2026
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-10-01334
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

4281 Meadow Lark Way
Owner: Quinn Fairley
Parcel 097-10-01334