Back to the backflow review queue
Backflow assembly test: 822 Laurel Dr
ApprovedFiled Jun 23, 2026 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 23, 2026
- Assembly type
- DC
- Serial number
- Z963561
- Size
- 1
- Test gauge serial
- G-4055
- Gauge calibration date
- Mar 5, 2025
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Ramirez, current on the service date
- All required fields present
- Address matches parcel 097-79-01247
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
822 Laurel Dr
Owner: Hayden Hollins
Parcel 097-79-01247