Back to the backflow review queue

Backflow assembly test: 9197 Hickory Trl

Approved

Filed May 17, 2026 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 17, 2026
Assembly type
RP
Serial number
B629953
Size
1
Test gauge serial
G-4897
Gauge calibration date
Dec 15, 2025
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-31-01264
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9197 Hickory Trl
Owner: Emerson Benton
Parcel 097-31-01264