Back to the backflow review queue
Backflow assembly test: 9168 Pine Knoll Ct
ApprovedFiled Aug 9, 2026 by Alex Kessler, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 9, 2026
- Assembly type
- DC
- Serial number
- K155252
- Size
- 1
- Test gauge serial
- G-6670
- Gauge calibration date
- May 6, 2026
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Kessler, current on the service date
- All required fields present
- Address matches parcel 097-14-01133
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9168 Pine Knoll Ct
Owner: Morgan Kessler
Parcel 097-14-01133