Backflow assembly test: 7905 Fox Run Dr
ApprovedFiled Jul 31, 2026 by Drew Okafor, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 31, 2026
- Assembly type
- DC
- Serial number
- Z297327
- Size
- 3/4
- Test gauge serial
- G-6093
- Gauge calibration date
- Jun 12, 2026
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Okafor, current on the service date
- All required fields present
- Address matches parcel 097-39-01221
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7905 Fox Run Dr
Owner: Drew Brandt
Parcel 097-39-01221