Backflow assembly test: 2994 Orchard Way
ApprovedFiled Dec 17, 2025 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 17, 2025
- Assembly type
- RP
- Serial number
- B809850
- Size
- 3/4
- Test gauge serial
- G-4282
- Gauge calibration date
- Jul 13, 2025
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Kessler, current on the service date
- All required fields present
- Address matches parcel 097-31-01262
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2994 Orchard Way
Owner: Emerson Stroud
Parcel 097-31-01262