Back to the backflow review queue
Backflow assembly test: 5708 Meadow Lark Way
ApprovedFiled Oct 28, 2026 by Logan Stroud, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 28, 2026
- Assembly type
- DC
- Serial number
- K529386
- Size
- 1
- Test gauge serial
- G-9964
- Gauge calibration date
- Sep 10, 2026
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Stroud, current on the service date
- All required fields present
- Address matches parcel 097-30-01042
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
5708 Meadow Lark Way
Owner: Quinn Nguyen
Parcel 097-30-01042