Backflow assembly test: 5476 Pine Knoll Dr
ApprovedFiled Mar 23, 2026 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 23, 2026
- Assembly type
- RP
- Serial number
- Z195209
- Size
- 3/4
- Test gauge serial
- G-6439
- Gauge calibration date
- Jun 25, 2025
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Ramirez, current on the service date
- All required fields present
- Address matches parcel 097-44-01128
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5476 Pine Knoll Dr
Owner: Reese Whitcomb
Parcel 097-44-01128