Backflow assembly test: 5476 Pine Knoll Dr

Approved

Filed Mar 23, 2026 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 23, 2026
Assembly type
RP
Serial number
Z195209
Size
3/4
Test gauge serial
G-6439
Gauge calibration date
Jun 25, 2025
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-44-01128
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5476 Pine Knoll Dr
Owner: Reese Whitcomb
Parcel 097-44-01128