Backflow assembly test: 4306 Spring Branch Way

Approved

Filed Mar 18, 2025 by Drew Lindqvist, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 18, 2025
Assembly type
PVB
Serial number
Z706020
Size
1
Test gauge serial
G-5241
Gauge calibration date
Dec 23, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 097-25-01261
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4306 Spring Branch Way
Owner: Blake Kessler
Parcel 097-25-01261