Backflow assembly test: Golden Elementary School

Filed Nov 24, 2026 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 24, 2026
Assembly type
RP
Serial number
W175330
Size
2
Test gauge serial
G-6985
Gauge calibration date
Jun 10, 2026
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ashby, current on the service date
  • All required fields present
  • Address matches parcel 095-99-01066
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

5829 Turkey Hill Trl
Owner: Kessler Holdings LLC