Backflow assembly test: Golden Elementary School
ApprovedFiled Nov 2, 2025 by Rowan Danner, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 2, 2025
- Assembly type
- RP
- Serial number
- W175330
- Size
- 2
- Test gauge serial
- G-8934
- Gauge calibration date
- Aug 13, 2025
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Danner, current on the service date
- All required fields present
- Address matches parcel 095-99-01066
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
5829 Turkey Hill Trl
Owner: Kessler Holdings LLC
Parcel 095-99-01066