Back to the backflow review queue

Backflow assembly test: Golden Bakery

Approved

Filed Sep 12, 2026 by Rowan Danner, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 12, 2026
Assembly type
RP
Serial number
B292191
Size
2
Test gauge serial
G-6367
Gauge calibration date
Feb 12, 2026
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Danner, current on the service date
  • All required fields present
  • Address matches parcel 095-33-01103
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1644 Laurel Way
Owner: Nguyen Holdings LLC
Parcel 095-33-01103