Backflow assembly test: 3263 Hickory Ln

Approved

Filed Feb 15, 2026 by Reese Whitcomb, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 15, 2026
Assembly type
RP
Serial number
K833517
Size
1
Test gauge serial
G-1379
Gauge calibration date
Aug 25, 2025
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 095-77-01041
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.