Back to the backflow review queue

Backflow assembly test: 8614 Sycamore Ct

Approved

Filed Sep 15, 2024 by Rowan Danner, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 15, 2024
Assembly type
PVB
Serial number
A507540
Size
1
Test gauge serial
G-8048
Gauge calibration date
Aug 6, 2024
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Danner, current on the service date
  • All required fields present
  • Address matches parcel 095-47-01155
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8614 Sycamore Ct
Owner: Drew Danner
Parcel 095-47-01155