Back to the backflow review queue

Backflow assembly test: 1522 Turkey Hill Ln

Approved

Filed May 12, 2024 by Morgan Benton, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
May 12, 2024
Assembly type
RP
Serial number
B948715
Size
1
Test gauge serial
G-2006
Gauge calibration date
Aug 12, 2023
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Benton, current on the service date
  • All required fields present
  • Address matches parcel 095-54-01252
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1522 Turkey Hill Ln
Owner: Hayden Marsh
Parcel 095-54-01252