Backflow assembly test: 1522 Turkey Hill Ln

Approved

Filed May 10, 2023 by Jamie Hollins, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
May 10, 2023
Assembly type
RP
Serial number
B948715
Size
1
Test gauge serial
G-6345
Gauge calibration date
Jan 16, 2022
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Hollins, current on the service date
  • All required fields present
  • Address matches parcel 095-54-01252
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1522 Turkey Hill Ln
Owner: Hayden Marsh
Parcel 095-54-01252