ApprovedFiled Jan 7, 2024 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 7, 2024
- Assembly type
- PVB
- Serial number
- A351291
- Size
- 3/4
- Test gauge serial
- G-6966
- Gauge calibration date
- Mar 25, 2023
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Ashby, current on the service date
- All required fields present
- Address matches parcel 095-13-01021
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.