Backflow assembly test: 3308 Mill Creek Ct

Approved

Filed Sep 26, 2025 by Reese Whitcomb, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 26, 2025
Assembly type
RP
Serial number
W527658
Size
1
Test gauge serial
G-3032
Gauge calibration date
Aug 12, 2024
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 095-67-01190
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.