Backflow assembly test: 2768 Laurel Trl

Approved

Filed Oct 23, 2026 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 23, 2026
Assembly type
PVB
Serial number
W160009
Size
3/4
Test gauge serial
G-9646
Gauge calibration date
Aug 20, 2026
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ashby, current on the service date
  • All required fields present
  • Address matches parcel 095-40-01264
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2768 Laurel Trl
Owner: Alex Benton
Parcel 095-40-01264