Back to the backflow review queue
Backflow assembly test: Crossroads Grill
ApprovedFiled May 17, 2024 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 17, 2024
- Assembly type
- RP
- Serial number
- A505743
- Size
- 4
- Test gauge serial
- G-7766
- Gauge calibration date
- Mar 6, 2024
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Ashby, current on the service date
- All required fields present
- Address matches parcel 095-35-01271
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8329 Quarry Ct
Owner: Calloway Holdings LLC
Parcel 095-35-01271