Backflow assembly test: 1364 Ridgeview Way

Approved

Filed Dec 8, 2025 by Reese Whitcomb, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 8, 2025
Assembly type
RP
Serial number
Z393707
Size
3/4
Test gauge serial
G-7442
Gauge calibration date
Nov 7, 2025
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 095-81-01345
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.