Backflow assembly test: 9261 Spring Branch Trl

Approved

Filed Sep 3, 2024 by Morgan Benton, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Sep 3, 2024
Assembly type
PVB
Serial number
Z114446
Size
3/4
Test gauge serial
G-1747
Gauge calibration date
Jul 22, 2024
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Benton, current on the service date
  • All required fields present
  • Address matches parcel 095-17-01148
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9261 Spring Branch Trl
Owner: Quinn Nguyen
Parcel 095-17-01148