Backflow assembly test: 4638 Turkey Hill Trl
ApprovedFiled Mar 23, 2024 by Morgan Benton, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Mar 23, 2024
- Assembly type
- DC
- Serial number
- A623233
- Size
- 1
- Test gauge serial
- G-9020
- Gauge calibration date
- Feb 7, 2024
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Benton, current on the service date
- All required fields present
- Address matches parcel 095-56-01140
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4638 Turkey Hill Trl
Owner: Jordan Vance
Parcel 095-56-01140