Back to the backflow review queue
Backflow assembly test: Golden Pizza
ApprovedFiled Nov 15, 2025 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 15, 2025
- Assembly type
- RP
- Serial number
- B393674
- Size
- 1 1/2
- Test gauge serial
- G-8511
- Gauge calibration date
- Oct 11, 2025
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-52-01041
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.