Backflow assembly test: 4179 Laurel Rd

Approved

Filed Oct 1, 2026 by Morgan Brandt, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Oct 1, 2026
Assembly type
RP
Serial number
Z428975
Size
3/4
Test gauge serial
G-2471
Gauge calibration date
Mar 22, 2026
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 093-86-01003
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4179 Laurel Rd
Owner: Hayden Nguyen
Parcel 093-86-01003