Backflow assembly test: Riverside Animal Hospital
ApprovedFiled Sep 17, 2025 by Drew Vance, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 17, 2025
- Assembly type
- RP
- Serial number
- W476046
- Size
- 1 1/2
- Test gauge serial
- G-1800
- Gauge calibration date
- Mar 10, 2025
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-85-01335
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.