Back to the backflow review queue

Backflow assembly test: 7038 Cedar Hollow Rd

Approved

Filed Jul 4, 2025 by Morgan Brandt, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Jul 4, 2025
Assembly type
PVB
Serial number
K158064
Size
1
Test gauge serial
G-6667
Gauge calibration date
Jun 25, 2024
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 093-20-01063
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7038 Cedar Hollow Rd
Owner: Alex Stroud
Parcel 093-20-01063