Backflow assembly test: 969 Pine Knoll Way

Approved

Filed Nov 10, 2024 by Jamie Ashby, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Nov 10, 2024
Assembly type
DC
Serial number
W598772
Size
1
Test gauge serial
G-8851
Gauge calibration date
Aug 23, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Ashby, current on the service date
  • All required fields present
  • Address matches parcel 093-75-01076
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

969 Pine Knoll Way
Owner: Cameron Whitcomb
Parcel 093-75-01076