Back to the backflow review queue
Backflow assembly test: Riverside Dental
ApprovedFiled May 7, 2026 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 7, 2026
- Assembly type
- RP
- Serial number
- W561269
- Size
- 1
- Test gauge serial
- G-3226
- Gauge calibration date
- Oct 7, 2025
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-32-01017
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
5179 Quarry Rd
Owner: Calloway Holdings LLC
Parcel 093-32-01017