Backflow assembly test: 9642 Sycamore Ct
ApprovedFiled May 29, 2025 by Reese Hollins, Lakeside Backflow Testing. Filed from a phone.
Report
- Date of service
- May 29, 2025
- Assembly type
- PVB
- Serial number
- W446974
- Size
- 3/4
- Test gauge serial
- G-5010
- Gauge calibration date
- Sep 27, 2024
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Hollins, current on the service date
- All required fields present
- Address matches parcel 093-49-01285
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9642 Sycamore Ct
Owner: Alex Calloway
Parcel 093-49-01285